Cancellation - Inter-regional transfer limit variation for Transient Stability Limit Victoria Region Tuesday, 24 May 2016
Cancellation - Inter-regional transfer limit variation for Transient Stability Limit Victoria Region Tuesday, 24 May 2016
The AEMO Dynamic Stability Analysis application is no longer indicating violations for a fault on a Hazelwood - South Morang 500 kV transmission line in the Victoria region. The following constraint set has been revoked at 0715hrs.
Constraint V-DSA_STAB-050
Constraints have the following interconnectors on the LHS
NSW1-QLD1
T-V-MNSP1
V-SA
V-S-MNSP1
VIC1-NSW1
Manager NEM Real Time Operations
Inter-regional transfer limit variation for Transient Stability Limit Victoria Region Tuesday, 24 May 2016
Inter-regional transfer limit variation for Transient Stability Limit Victoria Region Tuesday, 24 May 2016
The AEMO Dynamic Stability Analysis application is indicating violations for a fault on a Hazelwood - South Morang 500 kV transmission line in the Victoria region. The following constraint set has been invoked to apply offset reduction to the Victoria transient stability export limit.
Constraint V-DSA_STAB-050 invoked from 0635 hrs until further notice.
Constraints have the following interconnectors on the LHS
NSW1-QLD1
T-V-MNSP1
V-SA
V-S-MNSP1
VIC1-NSW1
Manager NEM Real Time Operations
Cancellation - Inter-regional transfer limit variation for Transient Stability Limit Victoria Region Tuesday, 24 May 2016
Cancellation - Inter-regional transfer limit variation for Transient Stability Limit Victoria Region Tuesday, 24 May 2016
The AEMO Dynamic Stability Analysis application is no longer indicating violations for a fault on a Hazelwood - South Morang 500 kV transmission line in the Victoria region. The following constraints sets have been invoked to apply offset reductions to the Victoria transient stability export limit.
Constraint V-DSA_STAB-100 invoked from 0205 hrs to 0325 hrs.
Constraint V-DSA_STAB-050 invoked from 0325 hrs to 0610 hrs.
Constraints have the following interconnectors on the LHS
NSW1-QLD1
T-V-MNSP1
V-SA
V-S-MNSP1
VIC1-NSW1
Manager NEM Real Time Operations
Update - Inter-regional transfer limit variation for Transient Stability Limit Victoria Region Tuesday, 24 May 2016
Update - Inter-regional transfer limit variation for Transient Stability Limit Victoria Region Tuesday, 24 May 2016
The AEMO Dynamic Stability Analysis application is indicating violations for a fault on a Hazelwood - South Morang 500 kV transmission line in the Victoria region. The following constraints sets have been invoked to apply offset reductions to the Victoria transient stability export limit.
Constraint V-DSA_STAB-100 invoked from 0205 hrs to 0325 hrs.
Constraint V-DSA_STAB-050 invoked from 0325 hrs until further notice.
Constraints have the following interconnectors on the LHS
NSW1-QLD1
T-V-MNSP1
V-SA
V-S-MNSP1
VIC1-NSW1
Manager NEM Real Time Operations
Inter-regional transfer limit variation for Transient Stability Limit Victoria Region Tuesday, 24 May 2016
Inter-regional transfer limit variation for Transient Stability Limit Victoria Region Tuesday, 24 May 2016
The AEMO Dynamic Stability Analysis application is indicating violations for a fault on a Hazelwood - South Morang 500 kV transmission line in the Victoria region. The following constraint set has been invoked to apply offset reduction to the Victoria transient stability export limit.
Constraint V-DSA_STAB-100 invoked from 0205 hrs until further notice.
Constraints have the following interconnectors on the LHS
NSW1-QLD1
T-V-MNSP1
V-SA
V-S-MNSP1
VIC1-NSW1
Manager NEM Real Time Operations
Cancellation - Inter-Regional Transfer limit variation: F2 Transformer Victoria Region, 23 May 2016.
Cancellation - Inter-Regional Transfer limit variation: F2 Transformer Victoria Region, 23 May 2016.
Refer Market Notices 53461, 53465, 53502, 53503
To maintain power system security AEMO have applied a limit of 850 MVA to the F2 transformer in NEMDE. This limit has been removed.
This restriction on use of short term ratings for the F2 Transformer in the Victoria region is cancelled from 0002 hrs Tuesday 24th May
This restriction will affect the following interconnectors.
T-V-MNSP1
V-S-MNSP1
V-SA
VIC1-NSW1
Manager NEM Real Time Operations
Update - date revision to 2400 hrs 23 May 2016 - Inter-Regional Transfer limit variation: F2 Transformer Victoria Region.
UPDATE - Inter-Regional Transfer limit variation: F2 Transformer Victoria Region, 23 May 2016.
Refer Market Notice 53645 , 53461 and 53502.
To maintain power system security AEMO has now applied a limit of 850 MVA to the F2 transformer in NEMDE. The applied limit may change according to power system conditions.
This restriction is expected to apply until approximately 2400 hrs, 23 May 2016.
This restriction will affect the following interconnectors.
T-V-MNSP1
V-S-MNSP1
V-SA
VIC1-NSW1
CA_SPS_46545836_02 constraint was revoked at 0930 hrs.
Manager NEM Real Time Operations
Update - Inter-Regional Transfer limit variation: F2 Transformer Victoria Region.
UPDATE - Inter-Regional Transfer limit variation: F2 Transformer Victoria Region, 23 May 2016.
Refer Market Notice 53645 and 53461.
To maintain power system security AEMO has now applied a limit of 850 MVA to the F2 transformer in NEMDE. The applied limit may change according to power system conditions.
This restriction is expected to apply until approximately 2400 hrs, 23 November 2016.
This restriction will affect the following interconnectors.
T-V-MNSP1
V-S-MNSP1
V-SA
VIC1-NSW1
CA_SPS_46545836_02 constraint was revoked at 0930 hrs.
Manager NEM Real Time Operations
Inter-Regional Transfer limit variation: F2 Transformer Victoria Region.
Inter-Regional Transfer limit variation: F2 Transformer Victoria Region.
Refer AEMO Market Electricity Market Notice 53461
AEMO has been advised by AusNet that due to prior loading conditions the South Morang F2 transformer pre contingent and post contingent loading must not exceed 1000 MVA.
To maintain power system security and in order to achieve this outcome AEMO has now applied a limit of 1000 MVA to the F2 Transformer in NEMDE.
Constraint set CA_SPS_46545836_02 invoked at 0110 hrs
Constraints have the following interconnectors on the LHS
V-SA
VIC1-NSW1
Manager NEM Real Time Operations