Transgrid Project Assessment Draft Report: Maintaining compliance with performance standards applicable to protection relays

22/04/2024
Market Network Service Provider
StageProject Assessment Draft Report
ConvenorAEMO NSP
Initiated22/04/2024
Accepting submissions?Yes
Submissions close07/06/2024

Transgrid has published the Project Assessment Draft Report (PADR) for Maintaining compliance with performance standards applicable to protection relays. This RIT-T includes 419 protection relays at various locations on the ACT and NSW transmission network, based on their assessed condition. Publication of this PADR represents the second step in the RIT-T process.

The identified protection relays will reach the end of their technical life by 2027/28, with manufacturer support, access to spares and defects rates being the largest drivers for remediation. The risk of reliably protecting primary assets increases as technology becomes superseded by the manufacturer, manufacturer support ceases and spare parts become scarce.

Redundant protection schemes are required to ensure the transmission system is adequately protected as outlined in the Network Performance Requirement under Schedule 5.1 of the National Electricity Rules (NER), therefore the condition issues affecting the identified protection relays on the ACT and NSW transmission network must be addressed.

If the failure to provide functional protection schemes due to technology obsolescence is not addressed by a technically and commercially feasible credible option in sufficient time (by 2027/28), the likelihood of not recovering from secondary systems faults and not maintaining compliance with NER performance requirements will increase. The proposed investment will enable Transgrid to continue to meet the standards for secondary systems availability set out in the NER, and to avoid the impacts of taking primary assets out of service.

In the PADR Transgrid has presented one credible network option that would meet the identified need from a technical, commercial, and project delivery perspective. The optimal commercially and technically feasible option presented in this PSCR – Option 1 (individual replacement of 419 identified assets across 48 sites within the regulatory period) – is the preferred option to meet the identified need at this stage of the RIT-T.

Transgrid welcomes written submissions on materials contained in this PADR. Submissions are due on 7 June 2024.