Filter by category
Filter by Date
Reclassification of a Non-Credible Contingency Event: Farrell - John Butters 220 kV Line and the Farrell - Rosebery Tee Queenstown - Newton 110 kV Line in Tasmania due to Lightning.
Reclassification of a Non-Credible Contingency Event: Farrell - John Butters 220 kV Line and the Farrell - Rosebery Tee Queenstown - Newton 110 kV Line in Tasmania due to Lightning.
Lightning is occurring near the Farrell - John Butters 220 kV Line and the Farrell - Rosebery Tee Queenstown - Newton 110 kV Line.
AEMO considers the simultaneous trip of those circuits to now be more likely.
Therefore AEMO has reclassified this as a credible contingency event from 0005 hrs 05/12/16 until further notice.
Manager NEM Real Time Operations
Reclassification of a Non-Credible Contingency Event: Farrell - Reece No. 1 and No. 2 220 kV Lines in Tasmania due to Lightning.
Reclassification of a Non-Credible Contingency Event: Farrell - Reece No. 1 and No. 2 220 kV Lines in Tasmania due to Lightning.
Lightning is occurring near the Farrell- Reece No. 1 and No. 2 220 kV Lines.
AEMO considers the simultaneous trip of those circuits to now be more likely.
Therefore AEMO has reclassified this as a credible contingency event from 2355 hrs 04/12/16 until further notice.
Constraint Set F-T-FARE_N-2 invoked.
Manager NEM Real Time Operations
Cancellation of the Reclassification of a Non-Credible Contingency Event: Chinchilla - Columboola 7349 and 7350 132 kV Lines in Queensland due to Lightning
Cancellation of the Reclassification of a Non-Credible Contingency Event: Chinchilla - Columboola 7349 and 7350 132 kV Lines in Queensland due to Lightning.
Refer AEMO Electricity Market Notice 56144
There is no longer any lightning activity in the vicinity of the Chinchilla - Columboola 7349 and 7350 132 kV Lines.
AEMO has cancelled the reclassification of the simultaneous trip of those circuits as a credible contingency event at 2240 hrs, 04/12/16.
Manager NEM Real Time Operations
Cancellation of the Reclassification of a Non-Credible Contingency Event: Tarong - Chinchilla 7183 and 7168 132 kV Lines in Queensland due to Lightning
Cancellation of the Reclassification of a Non-Credible Contingency Event: Tarong - Chinchilla 7183 and 7168 132 kV Lines in Queensland due to Lightning.
Refer AEMO Electricity Market Notice 56143
There is no longer any lightning activity in the vicinity of the Tarong - Chinchilla 7183 and 7168 132 kV Lines.
AEMO has cancelled the reclassification of the simultaneous trip of those circuits as a credible contingency event at 2240 hrs, 04/12/2016.
Manager NEM Real Time Operations
Inter-Regional Transfer Limit Variation - New South Wales Region - Directlink
Inter-Regional Transfer Limit Variation New South Wales Region Sunday, 04 December 2016 - Directlink
An unplanned outage of the Directlink DC No. 1 Leg occurred at 2141 hrs
The following constraint set invoked from 2150 hrs.
N-X_MBTE_2
The outage constraint set contains the following interconnector on the left hand side.
N-Q-MNSP1
See AEMO Network Outage Scheduler (NOS) for details.
Manager NEM Real Time Operations
Reclassification of a Non-Credible Contingency Event: Chinchilla - Columboola 7349 and 7350 132 kV Lines in Queensland due to Lightning.
Reclassification of a Non-Credible Contingency Event: Chinchilla - Columboola 7349 and 7350 132 kV Lines in Queensland due to Lightning.
Lightning is occurring near the Chinchilla - Columboola 7349 and 7350 132 kV Lines.
AEMO considers the simultaneous trip of those circuits to now be more likely.
Therefore AEMO has reclassified this as a credible contingency event from 1920 hrs 4 Dec 2016 until further notice.
Manager NEM Real Time Operations
Reclassification of a Non Credible Contingency Event: Tarong - Chinchilla 7183 and 7168 132 kV lines in Queensland.
Reclassification of a Non Credible Contingency Event: Tarong - Chinchilla 7183 and 7168 132 kV lines in Queensland.
Lightning is occurring near the Tarong - Chinchilla 7183 and 7168 132 kV lines.
AEMO considers the simultaneous trip of those circuits to now be more likely.
Therefore AEMO has reclassified this as a credible contingency event from 1650 hrs Sunday, 4 December 2016 until further notice.
Manager NEM Real Time Operations
NON-CONFORMANCE NSW Region 4 December 2016
NON-CONFORMANCE NSW Region 4 December 2016
AEMO has declared a scheduled generating unit non-conforming
Unit: MP1
Duration: 0630 hrs 04/12/2016 to 0635 hrs 04/12/2016
Amount: -37 MW
Constraint: NC-N_MP1
Manager NEM Real Time Operations
NON-CONFORMANCE Region QLD1 Sunday, 4 December 2016
NON-CONFORMANCE QLD1 Region Sunday, 4 December 2016
AEMO declared a schedule generating unit non-conforming
Unit: STAN-3
Duration: 04/12/2016 01:35 to 04/12/2016 01:45
Amount: -58 MW
Constraint: NC-Q_STAN-3
Auto-generated on behalf of Manager NEM Real Time Operations